北京布莱迪BLD两线防爆压力变送器YSZA/YSZB
可现场指示和远传输出
两线防爆压力变送器YSZA/YSZB
Two-line explosion-proof pressure transmitter
YSZA(YSZ)标准防腐型 Standard corrosion proof
防爆合格证号CE042028
Explosion-proof eligibility certificate:
YSZB(YSZ)简易型 Facility style
产品简介PRODUCT OVERVIEW
我公司生产的两线防爆压力变送器具有现场指示和远传输出两个功能,两部分各自相互独立,显示部分为一波登管压力表,压力传感器和相应的电器组成两线压力变送器的输出部分。此产品被广泛应用于石油、化工、炼钢、化纤、制药等行业。
The two-line pressure transmitter has the functions of spot display and output distance. The display part is a bourdon tube pressure gauge and pressure transmitter,relevant apparatus to be the output part. This product is widely used in petrochemical,pharmacy, steel making and so on.
此产品为本质安全防爆型产品。是根据GB3836-83《爆炸性环境用防爆电器设备的有关规定》设计制造的,并通过国家指定的防爆检验部门检验,其防爆合格证编号为GBY91158。
The transmitters are intrinsically safe style designed and manufactured in accordance with the National Standard of GB3836-83 for the electric equipment used in hazardous areas. Certificate of quality No.,GBY91158
防爆标志为:Ex ib II CT5(853 简易型无防爆证)
Identification code: ib Ⅱ cT5 (Identification code : ib cT5 (without explosion-proof certificate for 853 facility style)
变送器与装在控制室里的关联设备或安全栅配套使用组成本质安全型防爆系统。
YSZA 防腐型适用于对腐蚀性的气体或液体的测量。
YSZA-corrosion-proof is to measure the caustic gas or liquid.
YSZA 简易型仪表内可充油,应用在有振动的场所。
YSZB-facility style is able to be filled with oil ,applied to the vibration surroundings.
本仪表还可以通过配接化学密封隔离体,用于对具有较强腐蚀性且黏度较大易结晶
的液体的测量。
The gauge also can be deployed with insulations to measure the caustic, ropy and
crystal medium.
性能特点Feature
● 选用进口测压传感器作为敏感元件,其产品精度高,反应快。
Imported sensor as measuring element with high accuracy and quick response;
● 采用国外成熟的电路设计,具有较强的稳定可靠性。
Designed with foreign advanced electric circuit for reliability and stability;
● 结构简单,体积小,重量轻,便于安装,维修和调试。
Compact, light, simple and easy for installation, maintenannce and operation;
● 在输出电信号的同时,现场可以直接读出压力值。
Pressure values can be read at the same time ofthe output of electric signal.
主要技术参数Specifications
测量范围:0.1~60MPa;(简易型 0.1-25MPa) -0.1~0MPa;-0.1~2.4MPa
Range:0.1~60MPa;(Facility type 0.1-25MPa) -0.1~0MPa;-0.1~2.4MPa
连接尺寸:M20 × 1.5 阳螺纹(或其他特殊要求) 法兰连接 卫生隔膜连接
Connection:M20 × 1.5 male(or other requests) Flange connection Sanitary diaphragm connection
公称外径:φ 100mm / φ 150mm
Diameter:φ 100mm / φ 150mm
工作电压:24V.DC(+10%-5%)
Working voltage:24V.DC(+10%-5%)
输出信号:4~20mA.DC(1~5V.DC)
Signal output:4~20mA.DC(1~5V.DC)
精 度:输出信号± 0.5%, 现场显示± 1.5%
Accuracy:Signal output ± 0.5%,Local display ± 1.5%
负载电阻:(VS-12)/20(VS 工作电压)
Loading resistance:(VS-12)/20(VS Working voltage)
过压极限:130%
Overpressure limited:130%
使用温度:-10℃~+55℃
Working temperature:-10℃~+55℃
灵敏度温度附加误差:< 0.3%/10℃
Temperature error:< 0.3%/10℃
测压元件:陶瓷传感器
Element:Ceramic sensor
外壳:SUS304
Case:SUS304
度盘:铝合金,白底黑刻线
Dial:Aluminium alloy,black letters in white ground
玻璃:普通玻璃
Window:Common glass
接线盒:PVC
Junction box:PVC
防护等级:IP54(普通标准型) 充油耐震式IP65(简易型)
Protect class:IP54(standard type)Oil filled type IP65(Facility type)
防爆等级:ExibIICT5
Explosion-proof:ExibIICT5
防爆证号:CE042028Glass: Common glass
Explosion-proof certificate :CE042028
外型结构及安装方式Structure and installation
压力变送器应尽量安装在温度梯度和温度波动小的测压点上,同时还要避免考虑到振动和冲击的影响。变送器应直接安装在测量点上,但强腐蚀性的或过热的介质不应与变送器直接接触,需配装化学密封组件或散热器等进行隔离保护,再把取压口介质压力传输到变送器。
It is better to be installed to the place with little temperature fluctuate and avoid the vibration and concussion.To make sure the sealing of the connection part, it is better to wrap the adhesive tape before fixing the transmitter.It should be installed on the measuring point but not to touch the medium with strong corrupt and high temperature. It is better to make a transition by a special pipe.
负载特性Loading characters
系统连接及调试Connection and debugging
变送器在测量系统中的连接见图,建议电源电压Us 选用24V。
二次仪表中采样电阻(负载电阻)RL 的阻值选用250 Ω。如果Us 和RL 选用别的数值,那么RL 值不能超过由公式RL= 计算得到的数值。
See the chart as follow. Suggest the supply Us to be 24V.
The connected gauge should be RL=250Ω。If you choose other date for Us and RL,the RL can not exceedRL= .Use wires to seal the holes on the sides of the transmitter or install the signal wire to the holes and fix by tight nut. The hole without used should be sealed.
出厂前压力变送器已按订货要求调试合格,用户无需再做调整。长时间使用后如需重新标定,可分别调整“调零电位器”和“调量程电位器”。压力量程的下限值对应于4mA,上限值对应20mA. ( Z- 调零电位器 S-调量程电位器)
The transmitter has been debugged as the customer’s request, no need to debug again. After long time of using, if needed, it can be debugged by adjust“ Zero electric device” and“ Range electric device”. The down limit of the range should be corresponding with 4mA,and up limit will be with 20mA. (Z- Zero electric device, SRange electric device)
安 装Installation notes
1. 直接安装在测量点上(任意角度)。
Direct install to the measuring point(any angles).
2. 尽量安装在温度梯度与温度波动小的测压点上,同时避免强振动和冲击。
It is better to be with less temperature fluctuation and avoid the strong vibration.
3. 室外安装时,尽可能放置于保护盒内,避免阳光直射和雨淋,以保持变送器性能稳定和延长使用寿命。
If it is needed to install outside of the house, it is better to put it into a protect case to avoid sun and rain.
4. 测量蒸汽或其它高温介质时,注意不要使变送器的工作温度超限。必要时,请安装散热器或其它冷却装置连接。
While measuring the high temperature mediums, please do not exceed the temperature limitation. If necessary, fit it with cooling devices.
5. 安装时应在变送器和介质之间加装压力截止阀,以便检修和防止取压口堵塞而影响测量精度。在压力波动范围大的场合还应加装阻尼器或压力缓冲装置。
Add pressure cut-off valve between the transmitter and the medium and add the dampers if the pressure changes a lot.
如何选型 HOW TO ORDER YSZ
型号代码特性说明Code Introduction
基本型号Basic type
YSZA 二线制变送器(标准防腐型)Two-line pressure transmitter(Corrosion-proof)
YSZB 二线制变送器(简易型)Two-line pressure transmitter(facility-proof)
外 径Diameter
100 Ф 100mm
150 Ф 150mm
安 装 方 式Mounting
AO 径向直接安装Lower mounting direct
AH 径向后边Lower mounting with back side
量 程Ranges
M030 0.1MPa 其它请参看量程对照表See range table
连 接 螺 纹Connection
M20 20 × 1.5
Z12 NPT1/2”
备 选 项Options
T00 其他特殊要求的连接Other requests
FAA 一同配安全栅 With safe bar
FHG 配接化学密封隔离体 With chemical seals insulating body
BDA 压力指示1 级精度 Indicated accuracy: 1 class