NBN40-U1-Z2
菲尼克斯,Phoenix 销售热线 王勇 13661729801 021-51688715-8022 QQ:1594885782 传真:021-56503715
Technical Data: NBN40-U1-Z2
General specifications |
Switching element function | DCNO/NC |
Rated operating distance | 40 mm |
Installation | non-flush |
Output polarity | DC |
Assured operating distance | 0 ... 32.4 mm |
Reduction factor rAl | 0.3 |
Reduction factor rCu | 0.3 |
Reduction factor r304 | 0.7 |
Nominal ratings |
Operating voltage | 5 ... 60 V DC |
Switching frequency | 0 ... 100 Hz |
Hysteresis | typ. 5 % |
Reverse polarity protection | reverse polarity tolerant |
Short-circuit protection | yes |
Voltage drop | ≤ 5 V |
Operating current | 2 ... 200 mA |
Off-state current | 0 ... 0.5 mA |
Switching state indication | 2 LED, yellow |
Functional safety related parameters |
MTTFd | 1170 a |
Mission Time (TM) | 20 a |
Diagnostic Coverage (DC) | 0 % |
Approvals and certificates |
UL approval | cULus Listed, General Purpose |
CSA approval | cCSAus Listed, General Purpose |
CCC approval | Certified by China Compulsory Certification (CCC) |
Ambient conditions |
Ambient temperature | -25 ... 85 °C (-13 ... 185 °F) |
Mechanical specifications |
Connection type | screw terminals |
Core cross-section | max. 2.5 mm2 |
Housing material | PA/metal with epoxy powder coating |
Sensing face | PA |
Protection degree | IP68 / IP69K |
Mass | 225 g |
Note | Tightening torque: 1.8 Nm (housing) Tightening torque: 1.0 Nm (Screw
terminal) |