福建一级代理商长期供应 3000VA 华仪6830线性交流电源

Model| 6805 | 6810 | 6820 | 6830 | 6840 |
INPUT
Phase| 1 phase |
Voltage| 115/230Vac ± 15% | 230Vac ± 15% |
Frequency| 47-63Hz |
OUTPUT
Max. Power| 500VA | 1000VA | 2000VA | 3000VA | 4000VA |
Max Current(r.m.s)| 0-150V | 4.2A | 8.4A | 16.8A | 25.2A | 33.6A |
| 0-300V | 2.1A | 4.2A | 8.4A | 12.6A | 16.8A |
Max Current(r.m.s)
Opt. 0-600 V0-300V | 2.1A | 4.2A | 8.4A | 12.6A | 16.8A |
| 0-600V | 1.05A | 2.1A | 4.2A | 6.3A | 8.4A |
Phase| 1 phase / 2W |
Total Harmonic Distortation (T.H.D)| <=0.5% at 45-500Hz (Resistive Load) |
Crest Factor| >= 4 |
Line Regulation| ±0.1V |
Load Regulation| <=0.5% (Resistive Load) |
Response Time| < 100µS |
SETTING
Voltage| Range | 0-150V / 0-300V Selectable or 0-300V / 0-600V Selectable (Option 0 -600V) |
| Resolution | 0.1V |
| uracy | ±(0.5% of setting +2 counts) |
Frequency| Range | 45-500Hz |
| Resolution | 0.1Hz at 45.0-99.9Hz , 1Hz at 100-500Hz |
| uracy | ±0.02% of setting |
Frequency
(Option 45Hz - 1KHz)Range | 45-1000Hz |
| Resolution | 0.1Hz at 45.0-99.9Hz , 1Hz at 100-1000Hz |
| uracy | ±0.02% of setting |
MEASUREMENT
Frequency| Range | 45.0Hz - 500.0Hz 501.0Hz - 1000Hz (Opt.614) |
| Resolution | 0.1Hz |
| uracy | ±0.1Hz at 45.0 - 500.0Hz ±0.5Hz at 501.0 - 1000Hz |
Voltage| Range | 0.0-300.0V / 0.0-600.0V |
| Resolution | 0.1V |
| uracy | ± (0.5% of reading +2 counts) for 0-300V ± (0.5% of reading +4 counts) for 0-600V |
Current(r.m.s)| Range | L | 0.000-3.500A |
| H | 3.00-35.00A |
| Resolution | L | 0.001A |
| H | 0.01A |
| uracy | L | ± (0.5% of reading +5 counts) |
| H | ± (0.5% of reading + 3 counts) |
Power| Range | L | 0.0-350.0W |
| H | 300-4000W |
| Resolution | L | 0.1W |
| H | 1W |
| uracy | L | ± (0.6% of reading +5 counts) |
| H | ± (0.6% of reading +2 counts) |
Power Factor| Range | 0.000-1.000 |
| Resolution | W / VA ,Calculated and displayed to three significant digits |
| uracy |
GENERAL
Low Range Meter
(for 6805/ 6810 Option)Range : 2.0mA - 350.0mA / 0.20 - 35.00W Resolution : 0.1mA / 0.01W uracy : ± (0.6% of reading +5 counts). |
Remote Input Signal Interface
(Option)Test, Reset, Recall memory 1 through 7 |
Remote Output Signal| Fail ,Test-in Process |
Over Current Fold BackOn/Off , Setting On when output current over setting A-Hi value it will fold back output voltage to keep constant output current is setting A-Hi value. |
Protection| OCP, OTP ,OVP and Alarm |
Safety| TUV/GS pending |
Dimension(W x H x D) mm| 430 x 89 x 400,2U | 430 x 89 x 560,2U | 430 x 267 x 650,6U | 430 x 667 x 650,15U | 430 x 667 x 650,15U |
Net Weight| 25Kg | 36Kg | 90Kg | 165Kg | 192Kg |
Operation Environment0-40°C / 20-80%RH