The CW-24VD/VY was specifically designed with a 69 in. (1753 mm) height for use in 42U rack installations. The middle display and network connection allows the unit to be easily rotated if either busway or raised floor power is available.
The Switched CW-24VD/VY CDU combines remote configuration and management with power distribution, power monitoring and environmental monitoring. Reboot a single or dual-power server with one command. Receive SNMP alerts when power or environmental conditions exceed thresholds. Assign users specific access rights to designated outlets or groups. Choose one power distribution unit for your high-density cabinets.
Only our Switched CDU products provide the flexibility needed for all data centers and remote sites, including power requirements for high-amp, high voltage; UL 60950-1 branch circuit protection; SSL & SSH security; and SNMP-based input current monitoring.
产品图片:


产品特点:
| Sentry Cabinet PDU Specifications | |||||
| Item # | Available Input Voltages | Rated Amperage | Available Input Cord | Outlets | Dimensions (L x W x D) |
| CW-24VD/VY 50/60A 12xC13 & 12xC19 | |||||
| CW-24VDX451A9 CX-24VDX451A9* | 240V, 3-Phase Delta, 50/60Hz | 60A | IEC Blue 9hr 3P+G Plug, 10'(3m), Top/Frt Cord | (12) IEC 60320/C13 (12) IEC 60320/C19 | 69.0 x 1.75 x 3.50 in. (1753 x 44 x 89 mm) |
| CW-24VDV451A9 CX-24VDV451A9* | 240V, 3-Phase Delta, 50/60Hz | 50A | CS8365C Plug, 10'(3m), Top/Frt Cord | (12) IEC 60320/C13 (12) IEC 60320/C19 | 69.0 x 1.75 x 3.50 in. (1753 x 44 x 89 mm) |
| CW-24VYY451A9 CX-24VYY451A9* | 208V, 3-Phase Wye, 50/60Hz | 60A | IEC Blue 9hr 3P+N+G Plug, 10'(3m), Top/Frt Cord | (12) IEC 60320/C13 (12) IEC 60320/C19 | 69.0 x 1.75 x 3.50 in. (1753 x 44 x 89 mm) |
| *CX refers to the Expansion Module | |||||
| Additional Features and Specifications | |||||
Standards | |||||
Inpidual or group outlet remote power control to cycle power and reboot any selected server(s) or other network device(s). Use TCP/IP (HTTP, HTTPS, SSH, Telnet, SNMP) or RS-232 to communicate with each Sentry Cabinet PDU and rectify locked-up network devices. Assign outlets to a group for control of dual-power supply servers and other gear with a single command. Create an unlimited number of groups with any combination of outlets associated to each group. Reduce Mean Time to Repair (MTTR) a failing server by controlling inpidual power outlet receptacles to reboot any selected server or other device.
HTTP/HTTPs Web Configuration & ControlUse the Sentry Web interface to configure each unit's network settings. SNMP traps for environmental & power thresholds and firmware updates. Also use the Web interface to monitor key values, including amperage load(s), temperature/humidity and other environmental conditions. SSL security provides a secure HTTPs connection.
SNMP Management & Event NotificationThe Sentry family of products supports the Simple Network Management Protocol (SNMP). This allows network management systems to use SNMP requests to retrieve information such as input power, temperature and humidity. The Sentry includes an SNMP v1 agent supporting standard MIB I and MIB II objects. A private enterprise MIB extension (Sentry3 MIB) is also supported to provide remote power control. SNMP traps can be generated for various events, including Input Current Load Thresholds (min & max), Temperature Thresholds (min & max), Humidity Thresholds (min & max), water indication, and closed contacts (cabinet doors open/close).
Add a Second TowerConnect an Expansion Cabinet PDU to this Smart Cabinet PDU to control two power input circuits and monitor power in the Data Center cabinet (inpidual or groups) under 1 IP address - our exclusive strategy for managing dual power-supply servers.
Zero U EnclosureA vertical enclosure that occupies Zero Vertical U of rack space in the equipment cabinet. It mounts on the back rails or in the cavity space of the cabinet.
Secure Access - SSH or SSL ProtectionSecure Shell (SSH), known as Secure Socket Shell, is a Unix-based command interface and protocol for securely getting access to a remote device. Sentry supports SSHv2. Secure Sockets Layer (SSL) is a commonly-used protocol for managing the security of a message transmission on the Internet. SSL is an integral part of most Web browsers (clients) and Web servers. Sentry supports SSLv3/TLSv1.
Integrated Temp/Humidity Probe SupportTwo (2) RJ-style connectors located on the face panel of the PDU's enclosure provide support for two (2) Integrated Temperature & Humidity Probes with ten-foot (10') cables provide real-time measurements in the data center cabinet.
Firmware Flash UpgradeableAccess new firmware updates via FTP for new firmware features and code releases. An update to the firmware does not affect the status of the power outlets.
Click here for the latest Firmware update.
The sentry family of products supports Lightweight Directory Access Protocol (LDAP) Version 3 including LDAPS (LDAP over TSL/SSL). This support enable authentication with LDAP servers; user accounts do not need to be inpidually created locally on each Sentry device.
This allows administrators to pre-define and configure (in each Sentry product, and in the LDAP server) a set of necessary LDAP groups, and access rights for each. User's access rights can then be assigned or revoked simply by making the user a member of one or more pre-defined Sentry LDAP groups. User account can be added, deleted, or changed in the LDAP server without any changes on inpidual Sentry products.
Sentry LDAP support has been tested in the following environments:
- Microsoft Active Directory (MSAD)
- Novell eDirectory (eDir)
- Open LDAP
Serial control via any device with a bi-directional serial port, including a PC, laptop, KVM switch, Console Port Access switch, or terminal server.