Jacob防爆尼龙电缆防水接头(JACOB-EX-nylon cable gland-PAzz/EX)
Jacob PERFECT Ex-cable gland 50.6xx PAzz/EX
>> Configuration
Dome nut: Polyamide PA6
Dust cap: Polyethylene PE-LD
Sealing ring / outer part: Polychloroprene-Nitrile rubber CR/NBR
Sealing ring / inner part: Evoprene TPE (from M20x1,5)
Gland body: Polyamide PA6
Connecting thread: metric, as per EN 60423
>> Properties
Equipment group: II
Category / Zone: 2G, 2D and 3G/ 1, 2, 21, 22
Type of protection: Ex e, increased safety, Ex tD A21 - Protection by enclosures
Cable installation: fixed
Temperature range: -20°C / +70 (M12 und M16)°C
Further information on page 23, -55°C / +70 (M20 bis M63) °C
Protection grade: IP66
Test standard: EN 60079-0 / EN 60079-7, EN 61241-0 / EN 61241-1
EC-Type certificate: PTB 99 ATEX 3101 X (M12 und M16)
PTB 99 ATEX 3128 X (M20 bis M63)
IECEx certificate: IECEx PTB 05.0004x
>> Features
RAL 9005Connecting thread standard length
AØCLSW1SW2HPart No.
| mm | mm | mm | mm | mm | Piece |
|
| M12x1,5 | 4 - 7 | 8 | 15 | 15 | 31 | 100 | 50.612 PASW/EX |
| M16x1,5 | 5,5 - 10 | 8 | 20 | 20 | 35,5 | 100 | 50.616 PASW/EX |
| M20x1,5 | 5,5 - 13 | 8 | 24 | 24 | 37 | 100 | 50.620 PASW/EX |
| M25x1,5 | 8 - 17 | 8 | 29 | 29 | 43 | 50 | 50.625 PASW/EX |
| M32x1,5 | 12 - 21 | 10 | 36 | 36 | 50 | 25 | 50.632 PASW/EX |
| M40x1,5 | 17 - 28 | 10 | 46 | 46 | 51 | 10 | 50.640 PASW/EX |
| M50x1,5 | 22 - 35 | 12 | 55 | 55 | 61,5 | 5 | 50.650 PASW/EX |
| M63x1,5 | 27 - 48 | 12 | 68 | 68 | 65,5 | 5 | 50.663 PASW/EX |
Connecting thread long
AØCLSW1SW2HPart No.
| mm | mm | mm | mm | mm | Piece |
|
| M12x1,5 | 4 - 7 | 12 | 15 | 15 | 35 | 100 | 50.612 PASWL/EX |
| M16x1,5 | 5,5 - 10 | 12 | 20 | 20 | 39,5 | 100 | 50.616 PASWL/EX |
| M20x1,5 | 5,5 - 13 | 13 | 24 | 24 | 42 | 100 | 50.620 PASWL/EX |
| M25x1,5 | 8 - 17 | 13 | 29 | 29 | 48 | 50 | 50.625 PASWL/EX |
| M32x1,5 | 12 - 21 | 15 | 36 | 36 | 55 | 25 | 50.632 PASWL/EX |
| M40x1,5 | 17 - 28 | 15 | 46 | 46 | 56 | 10 | 50.640 PASWL/EX |
| M50x1,5 | 22 - 35 | 16 | 55 | 55 | 65,5 | 5 | 50.650 PASWL/EX |
| M63x1,5 | 27 - 48 | 16 | 68 | 68 | 69,5 | 5 | 50.663 PASWL/EX |
RAL 5015
Connecting thread standard length
AØCLSW1SW2HPart No.
| mm | mm | mm | mm | mm | Piece |
|
| M12x1,5 | 4 - 7 | 8 | 15 | 15 | 31 | 100 | 50.612 PABL/EX |
| M16x1,5 | 5,5 - 10 | 8 | 20 | 20 | 35,5 | 100 | 50.616 PABL/EX |
| M20x1,5 | 5,5 - 13 | 8 | 24 | 24 | 37 | 100 | 50.620 PABL/EX |
| M25x1,5 | 8 - 17 | 8 | 29 | 29 | 43 | 50 | 50.625 PABL/EX |
| M32x1,5 | 12 - 21 | 10 | 36 | 36 | 50 | 25 | 50.632 PABL/EX |
| M40x1,5 | 17 - 28 | 10 | 46 | 46 | 51 | 10 | 50.640 PABL/EX |
| M50x1,5 | 22 - 35 | 12 | 55 | 55 | 61,5 | 5 | 50.650 PABL/EX |
| M63x1,5 | 27 - 48 | 12 | 68 | 68 | 65,5 | 5 | 50.663 PABL/EX |
Connecting thread long
AØCLSW1SW2HPart No.
| mm | mm | mm | mm | mm | Piece |
|
| M12x1,5 | 4 - 7 | 12 | 15 | 15 | 35 | 100 | 50.612 PABL/L/EX |
| M16x1,5 | 5,5 - 10 | 12 | 20 | 20 | 39,5 | 100 | 50.616 PABL/L/EX |
| M20x1,5 | 5,5 - 13 | 13 | 24 | 24 | 42 | 100 | 50.620 PABL/L/EX |
| M25x1,5 | 8 - 17 | 13 | 29 | 29 | 48 | 50 | 50.625 PABL/L/EX |
| M32x1,5 | 12 - 21 | 15 | 36 | 36 | 55 | 25 | 50.632 PABL/L/EX |
| M40x1,5 | 17 - 28 | 15 | 46 | 46 | 56 | 10 | 50.640 PABL/L/EX |
| M50x1,5 | 22 - 35 | 16 | 55 | 55 | 65,5 | 5 | 50.650 PABL/L/EX |
| M63x1,5 | 27 - 48 | 16 | 68 | 68 | 69,5 | 5 | 50.663 PABL/L/EX |
Blue dome nut = specific marking for type of protection Ex i - intrinsic safety