2.1、性能参数:The performance parameters
表Table 1
名称 Name | 型号 Type | 工作压力范围 Working pressure | 额定工作压力rated working pressure | 储罐容量 Storage tank volume | 混合比 Mixing ratio | 流量范围 The range of flow | 射程 Range | 进出口压差 Differential pressure between inlet and outlet |
消防水/泡沫软管站 Fire water / foam hose reel station | PJP-8 | 0.6-1.2MPa | 0.7 MPa | 100~700L(可根据实际工程确定) According to the actual engineering | 3%或6% | 8L/s±8% | ≥18m | ≤0.2MPa |
PJP-16 | 16L/s±8% |
表Table 2
名称Name | 型号Type | 工作压力范围 Working pressure | 额定工作压力Rated working pressure | 流量范围 The range of flow | 射程 Range |
消防水软管站 Fire water hose reel station | SJP-8 | 0.6-1.2MPa | 0.7 MPa | 8L/s±8% | ≥18~28m |
SJP-16 | 16L/s±8% |
3.1、消防软管站装置的安装
消防水/泡沫软管站的底撬与甲板机座用螺栓紧固。
三、Installation and debugging of equipment
3.1、The installation of fire hose reel station device
Connect the bottom skid of fire water/foam hose reel station and deck engine base with bolts
3.2、泡沫灭火剂的充装
开启泡沫箱上的加液盖,用30-50L的量桶加泡沫液,液位高度可从加液口处观察,泡沫液加满后旋紧加液盖即可。
3.2. The filling of foam fire extinguishing agent
Open the filler plug on the foam tank, and then adding the foam liquid with 30-50 litre bucket, the height of liquid level can be observed from the filler opening, tighten the cover after foam liquid in a full tank.
3.3、消防泡沫软管站试验
3.3.1拉开软管卷盘,手持泡沫枪,打开消防水阀门,消防水进入比例混合器与泡沫液混合,1秒后即有泡沫混合液从末端流出(时间长短视管网的容积及末端试验产品的流量情况不同而不同),流至地面形成一层厚厚的泡沫液.