赖晚兵 13661709198微信同号 qq:2851001710
General specifications
Signal type | Digital Input |
Functional safety related parameters
Safety Integrity Level (SIL) | SIL 2 |
Supply
Connection | Power Rail or terminals 9+, 10- |
Rated voltage | 19 ... 30 V DC |
Ripple | ≤ 10 % |
Rated current | 20 ... 15 mA |
Power dissipation | ≤ 700 mW including maximum power dissipation in the output |
Input
Connection side | field side |
Connection | terminals 1+, 2- |
Rated values | acc. to EN 60947-5-6 (NAMUR) |
Open circuit voltage/short-circuit current | approx. 10 V DC / approx. 8 mA |
Switching point/switching hysteresis | 1.2 ... 2.1 mA / approx. 0.2 mA |
Line fault detection | breakage I ≤ 0.1 mA , short-circuit I ≥ 6.5 mA |
Pulse/Pause ratio | min. 100 µs / min. 100 µs |
Output
Connection side | control side |
Connection | output I: terminals 5, 6 ; output II: terminals 7, 8 |
Rated voltage | 30 V DC |
Rated current | 50 mA |
Response time | ≤ 200 µs |
Signal level | 1-signal: (external voltage) - 3 V max. for 50 mA 0-signal: blocked output (off-state current ≤ 10 µA) |
Output I | signal ; Transistor |
Output II | signal or error message ; Transistor |
Collective error message | Power Rail |
Transfer characteristics
Switching frequency | ≤ 5 kHz |
Galvanic isolation
Input/Output | reinforced insulation acc. to EN 50178, rated insulation voltage 300 Veff |
Input/power supply | reinforced insulation acc. to EN 50178, rated insulation voltage 300 Veff |
Output/power supply | basic insulation according to EN 50178, rated insulation voltage 50 Veff |
Output/Output | basic insulation according to EN 50178, rated insulation voltage 50 Veff |
Indicators/settings
Display elements | LEDs |
Control elements | DIP-switch |
Configuration | via DIP switches |
Labeling | space for labeling at the front |
Directive conformity
Electromagnetic compatibility | |
| Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) |
Conformity
Electromagnetic compatibility | NE 21:2011 |
Degree of protection | IEC 60529:2001 |
Protection against electrical shock | IEC 61010-1:2010 |
Input | EN 60947-5-6:2000 |
Ambient conditions
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) |
Mechanical specifications
Degree of protection | IP20 |
Connection | screw terminals |
Mass | approx. 100 g |
Dimensions | 12.5 x 114 x 119 mm (0.5 x 4.5 x 4.7 inch) , housing type A2 |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
Data for application in connection with hazardous areas
EU-type examination certificate | BASEEFA 13 ATEX 0080 |
| Marking | II (1)G [Ex ia Ga] IIC II (1)D [Ex ia Da] IIIC I (M1) [Ex ia Ma] I |
| Input | Ex ia |
| Voltage | 10.5 V |
| Current | 17.1 mA |
| Power | 45 mW (linear characteristic) |
Supply | |
| Maximum safe voltage | 253 V AC (Attention! Um is no rated voltage.) |
Output | |
| Maximum safe voltage | 253 V AC (Attention! The rated voltage can be lower.) |
Certificate | CML 19 ATEX 4410 X |
| Marking | II 3G Ex ec IIC T4 Gc |
Galvanic isolation | |
| Input/Output | safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V |
| Input/power supply | safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V |
Directive conformity | |
| Directive 2014/34/EU | EN IEC 60079-0:2018 , EN 60079-7:2015+A1:2018 , EN 60079-11:2012 |
International approvals
UL approval | |
| Control drawing | 116-0374 (cULus) |
IECEx approval | IECEx BAS 13.0046 IECEx CML 19.0147X |
| Approved for | [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I Ex ec IIC T4 Gc |
General information
Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |