ABC干粉灭火器适用于扑灭以下初起火灾:
A:普通固体材料火 B:可燃液体火 C:气体和蒸汽火 E:带电物质火
主要技术参数:
| 药剂充装量(kg) | 驱动气体 | 20℃工作压力(mpa) | 有效喷射距离(m) | 有效喷射时间(s) | 喷射剩余率(%) | 最小爆破压力(mpa) | 外型尺寸 ФxH(mm) | 总重量(kg) |
MFZ/ABC1 | 1±5% | N2 | 1.2 | ≥3 | ≥8 | ≤15 | ≥5.5 | 90x291 | 1.7 |
MFZ/ABC2 | 2±3% | N2 | 1.2 | ≥3.5 | ≥8 | ≤15 | ≥5.5 | 110x315 | 3.2 |
MFZ/ABC3 | 3±3% | N2 | 1.2 | ≥3.5 | ≥13 | ≤15 | ≥5.5 | 133x418 | 5 |
MFZ/ABC4 | 4±2% | N2 | 1.2 | ≥4.5 | ≥13 | ≤15 | ≥5.5 | 133x477 | 6.25 |
MFZ/ABC5 | 5±2% | N2 | 1.2 | ≥4.5 | ≥13 | ≤15 | ≥5.5 | 140x528 | 7.3 |
MFZ/ABC8 | 8±2% | N2 | 1.2 | ≥5.5 | ≥14 | ≤15 | ≥5.5 | 163x645 | 12.2 |
| P A S S---Pull,Aim,Squeeze,and Sweep |
| | Pullthe pin at the top of the extinguisher that keeps the handle from being Accidentally presed. |
拔出灭火器顶端的插销。 |
|
| | Aimthe nozzle toward the base of the fire 喷粉管对准火焰的根部。 |
|
| | Stand approximately 8 feet away from the fire andsqueezethe handle to discharge the extinguisher.If you release the handle.the discharge well stop. 离火源适当的距离按下压把灭火器开始喷射,松开压把停止喷射。 |
|
| | Sweepthe nozzle back and forth at the base of the fire.After the fire appears to be out,watch it carefully since it may re-ingnite! 喷射时对准火源根部左右摆动喷粉管一直到火完全熄灭。 |
|
灭火器维护保养注意事项:
1、 灭火器是通过内部的压力驱动灭火药剂来灭火,运输存放时应避免碰撞。放置处应保持干燥、通风, 防止受潮;应避免日光暴晒及强辐射热的作用,以免影响灭火器的正常使用;
2、 灭火器的存放环境温度应在-10°C ~+45°C ;
3、 灭火器开始要进行检查,以后每间隔2个月检查,若发现保险销遗失、灭火剂有泄漏、压力指示器不在绿色的工作范围内、距生产日期超过2年、灭火器表面有明显损坏,请及时联系当地灭火器产家。
4、 灭火器一经开启,即使喷出不多,也必须按规定要求进行再充装。再充装应送往灭火器厂家按规定的要求和方法进行充装,不得随便更换灭火剂品种、重量和驱动气体种类及压力;
5、 灭火器每次再冲装前,其主要受压部件,如器头、筒体应按规定进行2.1Mpa水压试验,合格者方可继续使用。水压试验不合格,应报废,不准用焊接等方法进行修复使用;
6、 灭火器不论使用还是未使用,距出厂月期满五年,必须送到厂家进行水压试验,合格后方可使用,以后每隔两年进行一次水压试验。
7、经维修充装的火器,应贴有消防监督部门认可合格证,并注上维修单位的名称和维修日期。