西门子LFL1...系列燃气燃烧器控制器LFL1.322

LFL1...系列燃气燃烧器控制器
| LFL1.122 Series 02 | LFL1.133 Series 02 | LFL1.322 Series 02 | LFL1.333 Series 02 | LFL1.335 Series 01 | LFL1.622 Series 02 | LFL1.635 Series 01 | LFL1.638 Series 01 | t1 | 10 | 9 | 36 | 31.5 | 37.5 | 66 | 67.5 | 67.5 | t2 | 2 | 3 | 2 | 3 | 2.5 | 2 | 2.5 | 2.5 | t2’ | - | 3 | - | - | 5 | - | 5 | 5 | t3 | 4 | 3 | 4 | 6 | 5 | 4 | 5 | 5 | t3’ | - | - | - | - | 2.5 | - | 2.5 | 2.5 | t4 | 6 | 6 | 10 | 12 | 12.5 | 10 | 12.5 | 12.5 | t4’ | - | - | - | - | 15 | - | 15 | 15 | t5 | 4 | 3 | 10 | 12 | 12.5 | 10 | 12.5 | 12.5 | t6 | 10 | 14.5 | 12 | 18 | 15 | 12 | 15 | 15 | t7 | 2 | 3 | 2 | 3 | 2.5 | 2 | 2.5 | 2.5 | t8 | 30 | 29 | 60 | 72 | 78 | 96 | 105 | 105 | t9 | 2 | 3 | 2 | 3 | 5 | 2 | 5 | 7.5 | t10 | 6 | 6 | 8 | 12 | 10 | 8 | 10 | 10 | t11 | optional | optional | optional | optional | optional | optional | optional | optional | t12 | optional | optional | optional | optional | optional | optional | optional | optional | t16 | 4 | 3 | 4 | 6 | 5 | 4 | 5 | 5 | t13 | 10 | 14.5 | 12 | 18 | 15 | 12 | 15 | 15 | t20 | 32 | 60 | - | 27 | 22.5 | - | - | - |
|
t1 | 预吹扫时间,风门打开 | t7 | 从开始到端口7开始工作的间隔时间(风机2开始延迟时间) | t2 | 安全时间 | t8 | 启动持续时间(没有端口11和12) | t2’ | 安全时间或1段火安全时间 | t9 | 第二安全时间 | t3 | 预点火时间,短(点火变压器连接端口16) | t10 | 从启动到空气压力监测开始的间隔时间(不包括风门运行时间) | t3’ | 预点火时间,长(点火变压器连接端口15) | t11 | 风门打开到最大位的运行时间 | t4 | 从t2开始到端口19打开2段火的间隔时间 | t12 | 风门运行到小火位的时间 | t4’ | 从t2’开始到端口19打开2段火的间隔时间 | t13 | 允许的燃烧后时间 | t5 | 从t4结束到端口20打开比例控制或阀门的间隔时间 | t16 | 直到风门给出打开命令的间隔时间 | t6 | 后吹扫时间(带风机2) | t20 | 程控器锁定后的顺序自检时间 |
|