0.6/1kV XLPE Insulation Power Cable
Application
LV XLPE is composed of compacted Cu or AI conductor, insulation layer and protection layer.In the process of cross linking,the PE particle changes from linear structure to 3D net structure,increasing its mechanical features,thermal aging and adaptation to environmental conditions,as well as keeping good electric performance.
The design conforms to Chinese standard GB/T12706-2002 and IEC60502.The XLPE insulated cable works at 90℃.They have good electrical features, high-temperature capability, big transmission volume, simple structure, small outer diameter, light weight, easy installation, and without level difference limitation.They are widely used in factories and city grids
Usage conditions
1. Ambient temperature is not lower than 0℃ (should be pre-heated if lower than 0℃),not limit of level difference.
2.Min.bending radius at installation:
Single-core without armoring:20D;
3-core without armoring:15D;
Single-core with armoring:15D;
3-core with armoring:12D;
(D is the outer diameter of the cable).
3.Cable working temperature:
PVC sheath no more than 90℃,
PE sheath not more than 80℃.
4.The maximum rated temperature is 90℃, not more than 250℃C in the case of short-circuit (1asting 5s max).
5.One or two single-core cable are not allowable laid up in the iron pipes