Article No. |
6GK7 343-1GX31-0XE0 |
|
Product-type designation |
CP 343-1 Advanced |
|
Transmission rate |
|
|
Transfer rate |
|
|
|
10 … 1 000 Mbit/s |
|
|
10 … 100 Mbit/s |
|
Interfaces |
|
|
Number of electrical connections |
|
- at interface 1 in accordance with Industrial Ethernet
|
1 |
- at interface 2 in accordance with Industrial Ethernet
|
2 |
|
|
1 |
|
Design of electrical connection |
|
- at interface 1 in accordance with Industrial Ethernet
|
RJ45 port |
- at interface 2 in accordance with Industrial Ethernet
|
RJ45 port |
|
|
|
|
design of the removable storage C-PLUG |
Yes |
|
Supply voltage, current consumption, power loss |
|
|
Type of supply voltage |
DC |
|
Supply voltage |
|
|
|
5 V |
|
|
24 V |
|
Relative positive tolerance at 24 V with DC |
20 % |
|
Relative negative tolerance at 24 V with DC |
15 % |
|
Consumed current |
|
- from backplane bus at 5 V for DC Typical
|
0.14 A |
- from external supply voltage at 24 V with DC
|
|
|
|
0.48 A |
|
|
0.62 A |
|
Resistive loss |
14.7 W |
|
Permitted ambient conditions |
|
|
Ambient temperature |
|
- for vertical installation during operating phase
|
0 … 40 °C |
- for horizontal installation during operating phase
|
0 … 60 °C |
|
|
-40 … +70 °C |
|
|
-40 … +70 °C |
|
|
- |
|
Relative humidity at 25 °C without condensation during operating maximum |
95 % |
|
Protection class IP |
IP20 |
|
Design, dimensions and weight |
|
|
Module format |
Compact module |
|
Width |
80 mm |
|
Height |
125 mm |
|
Depth |
120 mm |
|
Net weight |
0.8 kg |
|
Product properties, functions, components general |
|
|
Number of modules |
|
|
|
- |
|
|
- |
|
Performance data |
|
|
Performance data open communication |
|
|
Number of possible connections for open communication by means of SEND/RECEIVE blocks maximum |
16 |
|
Data volume |
|
- as user data per ISO connection for open communication by means of SEND/RECEIVE blocks maximum
|
8 Kibyte |
- as user data per ISO on TCP connection for open communication by means of SEND/RECEIVE blocks maximum
|
8 Kibyte |
- as user data per TCP connection for open communication by means of SEND/RECEIVE blocks maximum
|
8 Kibyte |
- as user data per UDP connection for open IE communication by means of SEND/RECEIVE blocks maximum
|
2 Kibyte |
|
Number of Multicast stations |
16 |
|
Performance data S7 communication |
|
|
Number of possible connections for S7 communication |
|
|
|
16 |
- with PG connections maximum
|
- |
- with PG/OP connections maximum
|
- |
|
|
- |
|
Performance data multi-protocol mode |
|
|
Number of active connections with multiprotocol mode |
48 |
|
Performance data IT functions |
|
|
Number of possible connections |
|
- as client by means of FTP maximum
|
10 |
|
|
|
|
|
2 |
|
|
4 |
|
|
1 |
|
Amount of data as useful data for e-mail maximum |
8 Kibyte |
|
Storage capacity of user memory |
|
- as flash memory file system
|
28 Mibyte |
|
|
30 Mibyte |
|
Number of possible write cycles flash memory cells |
100 000 |
|
Performance data PROFINET communication as PN IO-Controller |
|
|
Number of PN IO-Devices on PROFINET IO-Controller usable total |
128 |
|
Number of PN IO IRT-Devices on PROFINET IO-Controller usable |
128 |
|
Number of external PN IO lines with PROFINET per rack |
1 |
|
Data volume |
|
- as useful data for input variables as PROFINET IO controller maximum
|
4 Kibyte |
- as useful data for output variables with PROFINET IO controller maximum
|
4 Kibyte |
- as useful data for input variables per PN IO device with PROFINET IO controller maximum
|
1 433 byte |
- as useful data for output variables per PN IO device with PROFINET IO controller maximum
|
1 433 byte |
- as user data for input variable per PN IO device per submodule as PROFINET IO controller maximum
|
240 byte |
- as user data for output variables per PN IO device per submodule as PROFINET IO controller maximum
|
240 byte |
|
Performance data PROFINET communication as PN IO-Device |
|
|
Product function PROFINET IO device |
Yes |
|
Amount of data |
|
- as useful data for input variables as PROFINET IO device maximum
|
1 024 byte |
- as useful data for input variables as PROFINET IO device maximum
|
1 024 byte |
- as useful data for input variables for each sub-module under PROFINET IO device
|
240 byte |
- as useful data for input variables for each sub-module under PROFINET IO device
|
240 byte |
- as useful data for the consistency area for each sub-module
|
240 byte |
|
Number of submodules per PROFINET IO-Device |
32 |
|
Performance data PROFINET CBA |
|
|
Number of remote connection partners with PROFINET CBA |
64 |
|
Number of connections with PROFINET CBA total |
1 000 |
|
Amount of data |
|
- as useful data for digital inputs with PROFINET CBA maximum
|
8 192 byte |
- as useful data for digital outputs in the case of PROFINET CBA max.
|
8 192 byte |
- as useful data for arrays and data types
|
|
- in the case of acyclic transmission with PROFINET CBA maximum
|
8 192 byte |
- with PROFINET CBA with cyclic transmission maximum
|
250 byte |
- with PROFINET CBA in the case of local interconnection maximum
|
2 400 byte |
|
Performance data PROFINET CBA remote connection with acyclic transmission |
|
|
Updating time of the remote interconnections in the case of acyclic transmission with PROFINET CBA |
0.1 s |
|
Number of remote connections to input variables with acyclic transmission with PROFINET CBA maximum |
128 |
|
Number of remote connections to output variables with acyclic transmission with PROFINET CBA maximum |
128 |
|
Amount of data |
|
- as useful data for remote interconnections with input variables in the case of acyclic transmission with PROFINET CBA
|
8 Kibyte |
- as useful data for remote interconnections with output variables in the case of acyclic transmission with PROFINET CBA
|
8 Kibyte |
|
Performance data PROFINET CBA remote connection with cyclic transmission |
|
|
Update time of the remote interconnections with PROFINET CBA with cyclic transmission |
8 ms |
|
Number of remote connections to input variables with PROFINET CBA with cyclic transmission maximum |
200 |
|
Number of remote connections to output variables with PROFINET CBA with cyclic transmission maximum |
200 |
|
Amount of data |
|
- as useful data for remote interconnections with input variables with PROFINET CBA with cyclic transmission maximum
|
2 000 byte |
- as useful data for remote interconnections with output variables with PROFINET CBA with cyclic transmission maximum
|
2 000 byte |
|
Performance data PROFINET CBA HMI variables via PROFINET acyclic |
|
|
Number of connectable HMI stations for HMI variables with acyclic transmission with PROFINET CBA |
3 |
|
Updating time of the HMI variables in the case of acyclic transmission with PROFINET CBA |
500 ms |
|
Number of HMI variables with acyclic transmission with PROFINET CBA maximum |
200 |
|
Amount of data as useful data for HMI variables in the case of acyclic transmission with PROFINET CBA maximum |
8 Kibyte |
|
Performance data PROFINET CBA device-internal connections |
|
|
Number of internal connections with PROFINET CBA maximum |
256 |
|
Data volume of internal connections with PROFINET CBA maximum |
2 400 byte |
|
Performance data PROFINET CBA connections to constants |
|
|
Number of connections to constants with PROFINET CBA maximum |
200 |
|
Amount of data as useful data for interconnections with constants in the case of PROFINET CBA maximum |
4 096 byte |
|
Performance data PROFINET CBA PROFIBUS proxy functionality |
|
|
Product function with PROFINET CBA PROFIBUS proxy functionality |
No |
|
Product functions management, configuration |
|
|
Product function MIB support |
Yes |
|
Protocol is supported |
|
|
|
Yes |
|
|
Yes |
|
|
Yes |
|
Configuration software |
|
|
|
|
- for PROFINET CBA required
|
SIMATIC iMap V3.0 SP4 and higher |
|
Identification & maintenance function |
|
- I&M0 - device-specific information
|
Yes |
- I&M1 – higher level designation/location designation
|
Yes |
|
Product functions Diagnosis |
|
|
Product function Web-based diagnostics |
Yes |
|
Product functions switch |
|
|
Product feature switch |
Yes |
|
Product function |
|
|
|
No |
- for IRT PROFINET IO switch
|
Yes |
- Configuration with STEP 7
|
Yes |
|
Product functions Redundancy |
|
|
Product function |
|
|
|
Yes |
|
|
Yes |
- Media Redundancy Protocol (MRP)
|
Yes |
|
Product functions Security |
|
|
Design of the firewall |
stateful inspection |
|
Product function with VPN connection |
IPSec |
|
Type of encryption algorithms with VPN connection |
AES-256, AES-192, AES-128, 3DES-168, DES-56 |
|
Type of authentication procedure with VPN connection |
Preshared key (PSK), X.509v3 certificates |
|
Type of hashing algorithms with VPN connection |
MD5, SHA-1 |
|
Number of possible connections for VPN connection |
32 |
|
Product function |
|
- password protection for Web applications
|
Yes |
|
|
Yes |
- ACL - IP-based for PLC/routing
|
Yes |
- switchoff of non-required services
|
Yes |
- blocking of communication via physical ports
|
Yes |
- log file for unauthorized access
|
No |
|
Product functions Time |
|
|
Product function |
|
|
|
Yes |
- pass on time synchronization
|
Yes |
|
Protocol is supported NTP |
Yes |