RN2型户内高压限流熔断器,用于电力线路的过载及短路保护.所谓限流就是熔断器在短路电流达到峰值之前就将其切断的功能.
熔断特性:
当通过熔断器的电流为其额定电流的1.3倍时,1小时不熔断;
当通过熔断器的电流为其额定电流的2倍时,1小时内熔断
RN2型户内高压限流熔断器,用于电压互感器的保护,其断流容量为1000MVA。在短路时以限制线路电流到最小值的方式进行瞬时开断,1分钟内熔断电流应在0.6-1.8A范围内。
常用熔断器型号:
RW3-10/100A;RW3-10/200A;HRW3-10/100A;HRW3-10/200A;RW10-10F/100A;RW10-10F/200A;HRW10-10F/100A;HRW10-10F/200A;RW11-10/100A;RW11-10/200A;HRW11-10/100A;HRW11-10/200A;RW5-10/100A;HRW5-10/200A;RW7-10/100A;HRW7-10/200A;RW5-35/100A;HRW5-35/100A;PRWG2-35/100A;HPRWG2-35/100A;RW9-35/0.5A;RW10-35/100A;RWXO-35/0.5A;
XRNP1-10/0.5A;XRNP1-10/1A; XRNP1-10/2A;XRNP1-10/3A ;XRNP1-10/3.15A
;XRNP1-12/0.5A;XRNP1-12/1A ;XRNP1-12/2A; XRNP1-12/3A
;XRNP1-12/3.15A;XRNP1-35(40.5)/1-3.15A;XRNT1-10/3.15-40A;XRNT1-12/3.15-40A;XRNT1-10/50-100A;
XRNT1-12/50-100A;XRNT1-10(12)/125A; XRNT1-10(12/)160; XRNT1-10(12)/200A
;XRNT1-40.5/3.15-40A;XRNT1-35/3.15-40A;RN1-6(10)/2-25A;RN1-6(10)/30-75A;
RN2-6(10)/0.5-20A;RN2-6(10)/30-100A;RN3-10/100-200A
用途
本产品适用于户内外5Hz,额定电压3.6Kv系统及7.2Kv的系统,可与其它保护电器(开关、真空断路器等)配合使用,作为高压电动机及其它电力设备的过载或短路等的保护元件。
型号 技术参数及尺寸图
型号 | 额定电压Un(KV) | 额定电流In(A) | 直径×长度D×L(mm) | A(mm) | C(mm) | 额定开断电流(Kv) | 国外参考型号 | XRNM1 | 3.6 | 50 | φ51×254标准尺寸 | 337 | 305 | 63 | WDFHO | 63 | 80 | 100 | 125 | 160 | φ76×254标准尺寸 | WKFHO | 200 | 224 | 50 | 250 | 315 | 355 | 400 | 7.2/12 | 25 | φ76×403标准尺寸 | 486 | 454 | 63 | WFNHO | 31.5 | 40 | 50 | 63 | 80 | 100 | 125 | 160 | 200 | WKNHO | 224 | 250 | φ76×403 φ88×403
| 50 | 315 | 12 | 25 | φ76×600标准尺寸 | 682 | 650 | 63 | 31.5 | 40 | 50 | 63 | 80 | 100 | 125 | 160 | 50 | 200 | 224 |
四、技术参数及尺寸图 |