MODEL | 6303 | 6306 | 6309 | 6315 | 6330 | 6360 | 6390 | 63120 | 63150 | 63180 |
INPUT |
Phase*1 | 1ø | 3ø |
Voltage | 230Vac±15% | 220/380Vac±10% |
Frequency | 47-63Hz |
Max. Current*2 (approx) | 30A | 55A | 25A | 40A | 75A | 150A | 230A | 300A | 375A | 450A |
Power Factor | 0.7 | 0.8 |
AC OUTPUT |
Max. Power | Single-Phase | 1KVA | 2KVA | 3KVA | 5KVA | 10KVA | 20KVA | 30KVA | 40KVA | 50KVA | 60KVA |
Total Power | 3KVA | 6KVA | 9KVA | 15KVA | 30KVA | 60KVA | 90KVA | 120KVA | 150KVA | 180KVA |
Max. Current (r.m.s), | 0-150V | 8.4A | 16.8A | 25.2A | 42.0A | 84.0A | 168.0A | 252.0A | 336.0A | 420.0A | 504.0A |
Single-Phase*3 | 0-300V | 4.2A | 8.4A | 12.6A | 21.0A | 42.0A | 84.0A | 126.0A | 168.0A | 210.0A | 252.0A |
Max. Current (r.m.s), Single-Phase | 0-300V | 4.2A | 8.4A | 12.6A | 21.0A | 42.0A | 84.0A | 126.0A | 168.0A | 210.0A | 252.0A |
(Option 0 - 600V)*4 | 0-600V | 2.1A | 4.2A | 6.3A | 10.5A | 21.0A | 42.0A | 63.0A | 84.0A | 105.0A | 126.0A |
Phase | 3ø / 4W |
Total Harmonic Distortion (T.H.D) | < 1% at 47 - 63Hz (Resistive Load) |
Crest Factor | ≥3 |
Line Regulation | ± 0.1V |
Load Regulation | L - N : ± (0.5% of output + 0.5V) / L - L : ± (1% of output + 1V) at Resistive Load |
Deviation of phase angle | 120° ≤ ±1° at Load Balance, 120° ≤ ±2.5° at 100% Load Unblance |
Response Time | < 2 msec |
SETTINGS |
Voltage | Range | 0-150V/0-300V Selectable or 0-300V/0-600V Selectable(Option 0-600V) |
Resolution | 0.1V |
Accuracy | ±(1% of setting + 2counts) |
Frequency | Range | 47.0-63.0Hz Full Range Adjust |
Resolution | 0.1Hz |
Accuracy | ±0.02% of setting |
MEASUREMENT |
Voltage | L - N Range | 0.0-300.0V / 0.0-600.0V |
L - L Range | 0.0-520.0V / 0.0-1040V |
Resolution | 0.1V / 0.2V |
Accuracy*6 | ± (1% of reading + 2counts) |
Frequency | Range | 47.0 - 500.0Hz |
Resolution | 0.1Hz |
Accuracy | ±0.1Hz |
Current (r.m.s) | Range | L | 0.000-3.500A | 0.00-35.00A |
H | 3.00-35.00A | 30.00-350.0A |
Resolution | L | 0.001A | 0.01A |
H | 0.01A | 0.1A |
Accuracy | L | ± (1% of reading +5counts) | ± (1% of reading +2counts) |
H | ± (1% of reading +1count) | ± (1% of reading +1count) |
Current (r.m.s) | Range | L | 0.000-3.500A | 0.00-35.00A |
(Option 0-600V) | H | 3.00-35.00A | 30.00-350.0A |
| Resolution | L | 0.001A | 0.01A |
| H | 0.01A | 0.1A |
| Accuracy | L | ± (1% of reading +5counts) | ± (1% of reading +2counts) |
| H | ± (1% of reading +1count) | ± (1% of reading +1count) |
Power | Range | L | 0.0-350.0W | 0.000-3.500KW |
H | 300-4000W | 3.00-40.00KW |
Resolution | L | 0.1W | 0.001KW |
H | 1W | 0.01KW |
Accuracy | L | ± (1.5% of reading +5counts) |
H | ± (1.5% of reading +1count) |
Power Factor | Range | 0.000-1.000 |
Resolution | 0.001 |
Accuracy | W / V x A , Calculated and displayed to three significant digits |
GENERAL |
PLC Remote | I/P:ON/OFF, P1, P2, P3, O/P:Processing |
Memory | 8 Memoies, 5steps per memory for Voltage, Frequency, Test Time, Delay time and Current, Power, Power Factor Hi, Lo Limit setting |
Timer | 0 = Continuous, 1 - 9999 (Unit : sec, minute, hour selectable) |
Auto Loop Cycle | 0 = Continuous, OFF = Loop Once, 2 - 9999 (Unit : ×1, ×10, ×100) |
Auto Voltage Adjust | Enable it for improve voltage regulation within ±0.1V |
Efficiency | ≧80%(at Full Load ) | ≧85%(at Full Load ) |
Protection | Over Load, Short Circuit, Over Temperaturer, Over Voltage, Over Power and Alarm |
Calibration | Front Panel Calibration |
Interface (Option) | GPIB, USB & RS232 |
Operation Environment | 0 - 40℃ / 20 - 80%RH |
Dimension, mm*5 | W | 430 | 430 | 430 | 430 | 600 | 800 | 1200 | 1200 | 1600 | 1600 |
H | 602(709) | 602(709) | 732(839) | 732(839) | 842(949) | 1557(1707) | 1557(1804) | 1557(1804) | 1800 | 1800 |
D | 650(730) | 650(730) | 650(730) | 650(730) | 900(980) | 900(980) | 900(980) | 900(980) | 1100 | 1100 |
Dimension (PFC), mm*5 | W | 430 | 430 | 600 | 600 | 600 | 800 | 1200 | 1200 | - | - |
H | 732(839) | 732(839) | 732(839) | 732(839) | 842(949) | 1557(1707) | 1557(1804) | 1557(1804) | - | - |
D | 650(730) | 650(730) | 900(980) | 900(980) | 900(980) | 900(980) | 900(980) | 1100(1180) | - | - |
Net Weight | 130Kg | 145Kg | 171Kg | 207Kg | 366Kg | 497Kg | 820Kg | 1300Kg | 1800Kg | 2100Kg |
Net Weight (PFC) | 167Kg | 195Kg | 250Kg | 311Kg | 530Kg | 770Kg | 1200Kg | 1800Kg | - | - |
*1 No PFC function can be optioned for 1Ø input models | product specifications are subject to change without notice. |
*2 Max. Current without PFC Function |
*3 At working voltage 120V / 240V |
*4 At working voltage 240V / 480V |
*5 Figure in parentheses are maximum values |
*6 When output voltage < 30V, ADJ = ON can be meet this spec. |