terminals 1, 2-, 3+ suitable for Pt100, 2- and 3-wire connection
Lead resistance
max. 100 Ω per line
Measuring current
approx. 1 mA
Output
Connection side
control side
Connection
terminals 9+, 8-
Load
(U -12 V) / 0.02 A
Current output
4 ... 20 mA , limited to ≤ 35 mA
Fault signal
upscaling ≥ 22 mA (limited to 35 mA)
Transfer characteristics
Measurement range
span without linearization 25 ... 800 °C (77 ... 1472 °F)/with linearization 25 ... 375 °C (77 ... 707 °F), both adjustable zero point without linearization -200 ... 400 °C (-328 ... 752 °F)/with linearization -30 ... 375 °C (-22 ... 707 °F), both adjustable
Rise time
250 ms
Indicators/settings
Control elements
DIP-switch rotary switch
Configuration
via DIP switches via rotary switch
Labeling
space for labeling at the front
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EU
EN 61326-1:2013 (industrial locations)
Conformity
Insulation coordination
EN 50178
Galvanic isolation
EN 50178
Electromagnetic compatibility
NE 21
Degree of protection
IEC 60529
Ambient conditions
Ambient temperature
-20 ... 60 °C (-4 ... 140 °F)
Mechanical specifications
Degree of protection
IP20
Connection
screw terminals
Mass
approx. 150 g
Dimensions
20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) , housing type B2
Mounting
on 35 mm DIN mounting rail acc. to EN 60715:2001
Data for application in connection with hazardous areas