General specifications
| Signal type | Digital Input |
Functional safety related parameters
| Safety Integrity Level (SIL) | SIL 3 |
| Performance level (PL) | PL d |
Supply
| Connection | Power Rail or terminals 22+, 23+, 24- |
| Rated voltage | 20 ... 35 V DC |
| Ripple | ≤ 10 % |
| Rated current | ≤ 130 mA |
| Power dissipation | 2.1 W |
| Power consumption | max. 2.3 W |
Input
| Connection side | field side |
| Connection | terminals 10+, 12- |
| Open circuit voltage/short-circuit current | approx. 8.4 V DC / approx. 11.7 mA |
| Lead resistance | ≤ 50 Ω, in hazardous area cable capacitances and inductivities are to be taken into account |
| Switching point | |
| Relay de-energized | I 5.9 mA |
| Relay energized | 2.8 mA < I < 5.3 mA |
| Response delay | ≤ 1 ms |
Output
| Connection side | control side |
| Connection | output I: terminals 13, 14 ; output II: terminals 15, 21 ; output III: terminals 16+, 17- |
| Output I | relay , signal |
| Contact loading | 50 V AC/1 A/cos φ > 0.7; 24 V DC/1 A resistive load |
| Mechanical life | 50 x 106 switching cycles |
| Output II | relay , signal |
| Contact loading | 50 V AC/1 A/cos φ > 0.7; 24 V DC/1 A resistive load |
| Mechanical life | 50 x 106 switching cycles |
| Output III | electronic output, passive , fault signal |
| Rated voltage | 10 ... 30 V DC |
| Signal level | 1-signal: (L+) -2.5 V (7 mA, short-circuit proof) / 0-signal: blocked output (Leakage current ≤ 10 mA) |
Transfer characteristics
| Switching frequency | 5 Hz |
Indicators/settings
| Display elements | LEDs |
| Labeling | space for labeling at the front |
Directive conformity
| Electromagnetic compatibility | |
| Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) |
| Low voltage | |
| Directive 2014/35/EU | EN 61010-1:2010 |
| Machinery Directive | |
| Directive 2006/42/EC | EN/ISO 13849-1:2008 |
Conformity
| Electromagnetic compatibility | NE 21:2011 |
| Degree of protection | IEC 60529:2001 |
Ambient conditions
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) |
Mechanical specifications
| Degree of protection | IP20 |
| Connection | screw terminals |
| Mass | approx. 280 g |
| Dimensions | 40 x 107 x 115 mm (1.6 x 4.2 x 4.5 inch) , housing type C1 |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
Data for application in connection with hazardous areas
| EU-Type Examination Certificate | PTB 00 ATEX 2042 |
| Marking | II (1)GD [EEx ia] IIC [circuit(s) in zone 0/1/2] |
| Certificate | TÜV 99 ATEX 1493 X |
| Marking | II 3G Ex nA nC IIC T4 |
| Directive conformity | |
| Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 |
International approvals
| FM approval | |
| Control drawing | 116-0158 |