Type | AC version |
Electrical specifications
Nominal resistance | 12 Ω |
Series resistance | max. 27.27 Ω |
Fuse rating | 50 mA |
Hazardous area connection
Connection | terminals 1, 2; 2, 3; 2, 4 |
Safe area connection
Connection | terminals 5, 7; 6, 7; 8, 7 |
Working voltage | |
| Supply loop | max. 3.7 V |
| Measurement loop | max. 0.6 V at 1 µA |
Conformity
Degree of protection | IEC 60529 |
Ambient conditions
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) |
Storage temperature | -25 ... 70 °C (-13 ... 158 °F) |
Relative humidity | max. 75 % , without condensation |
Mechanical specifications
Degree of protection | IP20 |
Connection | screw terminals |
Core cross-section | max. 2 x 2.5 ... mm2 |
Mass | approx. 150 g |
Dimensions | 12.5 x 115 x 110 mm (0.5 x 4.5 x 4.3 inch) |
Construction type | modular terminal housing , see system description |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
Data for application in connection with hazardous areas
EU-Type Examination Certificate | BAS 01 ATEX 7005 |
| Marking | II (1)GD, I (M1) [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I (-20 °C ≤ Tamb ≤ 60 °C) [circuit(s) in zone 0/1/2] |
| Voltage | 4.5 V |
| Current | 383 mA |
| Power | 430 mW |
Supply | |
| Maximum safe voltage | 250 V |
Series resistance | min. 11.76 Ω |
Certificate | TÜV 99 ATEX 1484 X |
| Marking | II 3G Ex nA IIC T4 Gc [device in zone 2] |
Directive conformity | |
| Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 |
International approvals
FM approval | |
| Control drawing | 116-0118 |
UL approval | |
| Control drawing | 116-0139 |
CSA approval | |
| Control drawing | 116-0119 |
IECEx approval | IECEx BAS 09.0142 IECEx BAS 17.0091X |
| Approved for | [Ex ia Ga] IIC , [Ex ia Da] IIIC , [Ex ia Ma] I Ex ec IIC T4 Gc |
General information
Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |